ANVER Motor Starters are made for us in Italy to the highest quality standards. The motor circuit controller combines the function of:

  • Short circuit protection

  • Current overload protection
  • Switching
  • 3 phase

Ideal for group motor installations...

ANVER starters can eliminate the need for larger and more expensive fuse blocks and fused disconnects, or circuit breakers.

ANVER starters offer a wide application range, from 0.1 to 25 Full Load Amp (FLA). For group motor applications, ANVER starters have a group installation rating of up to 600V @ 2,000 Amp, one of the highest in the industry.

...or as a manual starter

ANVER starters are also excellent as manual motor starters that employ all of the same motor protection features in one compact unit. ANVER starters are available in a variety of enclosures including general purpose watertight the most compact on the market today).

In the event of a short-circuit, the contacts are opened by magnetic, non-adjusting tripping elements in times approaching 1/1000 of a second. Because of this superb current limiting capability, ANVER starters have a short-circuit capacity of up to 42kA at 600 V.

Because each ANVER starter is individually calibrated at the factory for the smallest and largest current, very accurate thermal overload protection is also obtained. Each motor starter now comes with an enclosure.

Motor Starter Specifications:
Horsepower ratings shown in the table below are for reference. The final selection of the manual starter depends on the actual motor full load current and service factor.

ANVER
Part No.

Amperage Range

Phase

Maximum HP

Minimum

Maximum

230V

460V

575V

ST-025-040

2.50

4.00

Three

3/4

2

3

ST-040-063

4.00

6.29

Three

2

5

N/A

ST-063-100

6.30

9.99

Three

3

N/A

ST-100-160

10.00

15.99

Three

5

10

N/A

ST-160-200

16.00

19.99

Three

15

N/A

ST-200-250

20.00

25.00

Three

15

20

ST-ENCL

Enclosure, for Motor Starters (fits all above sizes)

Appropriate Motor Starters for ANVER Vacuum Pumps:

ANVER Pump No.
(Click to View Photo)

HP

Recommended Starter No.
(Click to View Photo)

Voltage

Amps

Port Size

Hose
in.
(mm)

VB3HF

3.4 HP

ST-100-160

208-230

10

1-1/4"NPT

1-1/2
(38.1)

ST-040-063

460

5

ST-040-063

575

4

VB4HF

4.6 HP

ST-100-160

208-230

13.6

2" NPT

2
(50.8)

ST-063-100

460

6.8

ST-040-063

575

5

VB6

7.5 HP

ST-200-250

208-230

18.5

2" Barb

2
(50.8)

ST-063-100

460

8.6

ST-063-100

575

6.8

VB7HV

4.8 HP

ST-100-160

208-230

12.2

1-1/4"NPT

2
(50.8)

ST-063-100

460

6.1

ST-025-040

575

3.8

VB8HF

8.5 HP

ST-200-250

208-230

24

2" NPT

2
(50.8)

ST-100-160

460

12

ST-100-160

575

9.6

VB9HV

7.5 HP

ST-160-200

208-230

14.9

1-1/4"NPT

2
(50.8)

ST-063-100

460

7.5

ST-040-063

575

5.2

ANVER Corp.,  36 Parmenter Rd,  Hudson, MA  01749  USA  -  Tel: 800-654-3500  -  978-568-0221  -  Fax: 978-568-1570